DSCPS Series

              Control and Protection Switch

              (1-125A)

              Concise Efficient Safe Comprehensive

              PRODUCT OVERVIEW

              DSCPS series control and protection switch is a comprehensive intelligent product integrating various functions of circuit breaker (fuse), contactor, overload (overcurrent, phase failure) protection relay, starter, isolator, etc. It can protect the system from short-circuit, overload, and leakage protection, and it is widely used in industry and other fields to protect the circuits and realize intelligent control and management.

              MULTIPLE PROTECTION FUNCTIONS

              D5CPS series control and protection switch has many functions such as phase failure, overcurrent, locked rotor, blockage, short circuit, undercurrent, overvoltage, undervoltage, residual current protection, three-phase unbalance, phase loss, isolation, startup timeout, fire protection, fault signal output, and remote shunt, etc., providing electrical protection for the equipment.

              FAULT MEMORY FUNCTION

              DSCPS series control and protection switch has the functions of remote automatic control and local direct manual control. Various parameters can be set and queried; based on MCU's ERPROM storage memory technology, parameters can be saved after power failure. It has a fault memory function, which is convenient for fault query and analysis.

              Technical parameters

              DSCPS series control and protection switch technical parameters

              Shell frame grade Rated current
              of main body
              Breaking Casing grade
              capacity (kA)
              Rated operating
              current of
              controller Ie (A)
              Rated operating
              current adjustment
              range of
              controller Ir (A)
              Control power range of
              400V (kW) (kW)
              Use category
              45 16 15 1 0.2-1 0.12-0.37 Motor type AC-44
              3 1-3 0.55-1.5
              6 2.4-6 1.1-3
              10 4-10 1.5-4
              16 6.4-16 3-7.5
              45 20 10-20 5.5-11
              32 12.8-32 5.5-15
              45 16-45 7.5-18.5
              125 125 35 50 20-50 7.5-22
              63 25.2-63 11-30
              80 32-80 16-37
              100 40-100 22-45
              125 50-125 22-55

              DSCPS2 series control and protection switch technical parameters

              Shell frame grade Rated current of
              main body
              Breaking capacity(kA) Rated operating current
              of controller Ie (A)
              Rated operating
              current adjustment
              range of controller Ir (A)
              Control power
              range of 400V (kW) (kW)
              Use category
              45 16 50kA 1 0.2-1 0.12-0.37 Motor type AC-44
              4 1-4 0.55-1.5
              6.3 2.4-6.3 1.1-3
              12 4-12 1.5-4
              16 6.4-16 3-7.5
              45 32 12.8-32 5.5-15
              45 16-45 7.5-18.5
              125 63 45 18-45 7.5-18.5
              50 20-50 7.5-22
              63 25.2-63 11-30
              125 100 40-100 22-37
              125 50-125 22-55
              Selection table

              DSCPS Series Control and Protection Switch

              DSCPS 45 H 33 M 45 FK M B F
              Product code Shell frame
              grade
              Breaking
              capacity (kA)
              Number of
              poles and
              protection
              Tripping
              device code
              Rated
              current
              Auxiliary
              code
              Control
              voltage
              Display
              code
              Additional
              features
              DSCPS:
              Control and Protection Switch
              45A
              125A
              Ics:15kA
              Ics:35kA
              33: 3 pole 3 protection
              30:3 pole without protection
              M: Motor protection1A
              3A
              6A
              10A
              16A
              20A
              32A
              45A
              50A
              63A
              80A
              100A
              125A
              FK: 4 opened, 3 closed
              + 1 group conversion
              + 1 group fault alarm
              + 1 group short-circuit alarm
              M:AC220V B:Digital F:Fire protection
              L:Leakage
              FL:Fire protection+Leakage

              Note: Isolation function is standard setting

              DSCPS2 Series Control and Protection Switch

              DSCPS2 45 H 33 M 45 FK M B F
              Product code Shell frame
              grade
              Breaking capacity (kA) Number of
              poles and
              protection
              Tripping
              device code
              Rated current Auxiliary
              code
              Control voltage Display code Additional
              features
              DSCPS2:
              Control and Protection Switch
              45A
              125A
              Ics:50kA 33: 3 pole 3 protection
              30:3 pole without protection
              M: Motor protection 1A
              4A
              6.3A
              12A
              16A
              32A
              45A
              50A
              63A
              100A
              125A
              FK: 2 opened and 2 closed
              + 1 group conversion
              + 1 group short-circuit alarm
              M:AC220V B:Digital
              E:LCD
              F:Fire protection
              L:Leakage
              T:Communication
              FT:Fire protection+Communication
              TL:Communication+Leakage
              FLT:Fire protection+Leakage +Communication

              Note: Isolation function is standard setting, fire protection and leakage function are optional.

              Technical Parameters


              DSCPS Series Control and Protection Switch

              • Rated current of main body:16

                Breaking capacity (kA) :15kA

                Rated operating current of controller Ie (A) :1A、3A、6A、10A、16A

                Rated operating current adjustment range of controller Ir (A) :0.2-1A、1-3A、2.4-6A、4-10A、6.4-16A

                Control power range of 400V (kW) :0.12-0.37kW、0.55-1.5kW、1.1-3kW、1.5-4kW、3.7-5kW

                Use category: Motor type AC-44

              • Rated current of main body :45

                Breaking capacity (kA) :15kA

                Rated operating current of controller Ie (A) :20A、32A、45A

                Rated operating current adjustment range of controller Ir (A) :10-20A、12.8-32A、16-45A

                Control power range of 400V (kW) :5.5-11kW、5.5-15kW、7.8-18.5kW

                Use category: Motor type AC-44

              • Rated current of main body :125

                Breaking capacity (kA) :35kA

                Rated operating current of controller Ie (A) :50A、63A、80A、100A、125A

                Rated operating current adjustment range of controller Ir (A) :20-50A、25.2-63A、32-80A、40-100A、50-125A

                Control power range of 400V (kW) :7.5-22kW、11-30kW、16-37kW、22-45kW、22-55kW

                Use category: Motor type AC-44

              DSCPS2 Series Control and Protection Switch

              • Rated current of main body :16

                Breaking capacity (kA) :50kA

                Rated operating current of controller Ie (A) :1A、4A、6.3A、12A、16A

                Rated operating current adjustment range of controller Ir (A) :0.2-1A、1-4A、2.4-6A、4-12A、6.4-16A

                Control power range of 400V (kW) :0.12-0.37kW、0.55-1.5kW、1.1-3kW、1.5-4kW、3.7-5kW

                Use category: Motor type AC-44

              • Rated current of main body :45

                Breaking capacity (kA) :50kA

                Rated operating current of controller Ie (A) :32A、45A

                Rated operating current adjustment range of controller Ir (A) :12.8-32A、16-45A

                Control power range of 400V (kW) :5.5-15kW、7.8-18.5kW

                Use category: Motor type AC-44

              • Rated current of main body :63

                Breaking capacity (kA) :50kA

                Rated operating current of controller Ie (A) :45A、50A、63A

                Rated operating current adjustment range of controller Ir (A) :18-45A、20-50A、25.2-63A

                Control power range of 400V (kW) :7.8-18.5kW、7.5-22kW、11-30kW

                Use category: Motor type AC-44

              • Rated current of main body :125

                Breaking capacity (kA) :50kA

                Rated operating current of controller Ie (A) :100A、125A

                Rated operating current adjustment range of controller Ir (A) :40-100A、22-37A

                Control power range of 400V (kW) :22-37kW、22-55kW

                Use category: Motor type AC-44

              Selection table


              • Product code :DSCPS: Control and Protection Switch

                Casing grade:45A、125A

                Breaking capacity (kA) :Ics:15kA、Ics:35kA

                Number of poles and protection:33: 3 pole 3 protection 、30:3 pole without protection

                Tripping device code:M: Motor protection

                Rated current:1A、3A、6A、10A、16A、20A、32A、45A、50A、63A、80A、100A、125A

                Auxiliary code:FK: 4 opened, 3 closed+ 1 group conversion + 1 group fault alarm + 1 group short-circuit alarm

                Control voltage:M:AC220V

                Display code:B:Digital

                Additional features:F:Fire protection、L:Leakage 、FL:Fire protection+Leakage

              • Product code :DSCPS2: Control and Protection Switch

                Casing grade:45A、125A

                Breaking capacity (kA) :Ics:50kA

                Number of poles and protection:33: 3 pole 3 protection 、30:3 pole without protection

                Tripping device code:M: Motor protection

                Rated current:1A、4A、6.3A、12A、16A、32A、45A、50A、63A、100A、125A

                Auxiliary code:FK: 2 opened and 2 closed+ 1 group conversion + 1 group fault alarm

                Control voltage:M:AC220V

                Display code:B:Digital 、E:LCD

                Additional features:F:Fire protection、L:Leakage 、T:Communication、FT:Fire protection+Communication、TL:Communication+Leakage 、FLT:Fire protection+Leakage +Communication